SINGLE PHASE - DIRECT INPUT - M1DL-MID
Those energy meters used for billing should have MID Certification. Thus, the quality of the instruments is ensured having been necessary to control by a notified body that just it.
An electricity meter, electric meter, electrical meter, or energy meter is a device that measures the amount of electric energy consumed by a residence,
a business, or an electrically powered device.
1. SINGLE-PHASE.
2. ACCURACY CL.1 (EN 62053).
3. DIRECT MEASUREMENT UP TO 50 A.
4.INTERNAL SHUNT.
5. ENERGY CONSUMPTION LED.
6.7 DIGITS ELECTRONIC COUNTER.
7.PULSE OUTPUT SO (DIN 43864).
8. 1 DIN MODULE.
Rated Voltage (Un) | 230 V A.C. |
Burden | < 8 VA, 2 W |
Operating range | ± 15 % Un |
Frequency | 50 - 60 Hz |
TECHNICAL SPECIFICATIONS
VOLTAGE INPUT
Current IB (IMAX) | 5 (50) A |
Burden | < 1 VA |
Operating range | 0-100 % IMAX |
Starting current (In) | < 0,4 % IB |
CURRENT INPUT
GENERAL FEATURES
Counter type | LED Display |
Digits | 5 + 2 decimals |
Nº of counters | 1 (Total) |
Class | 1 ( EN 62053) |
Operating temperature | - 20 to +60 ºC |
Energy indicator | Energy indicator |
Pulse weight | 1000 pulses / kWh |
Case material | ABS, UL94 V0 |
Dimensions | 1 module (17,5 mm) |
Terminals | Sealable |
Connection | With screw |
Max. wire section | 2 12 mm |
Mounting | 35 mm DIN rail |
THREE-PHASE - DIRECT INPUT - TCIDL1
Those energy meters used for billing should have MID Certification. Thus, the quality of the instruments is ensured having been necessary to control by a notified body that just it.
1. SINGLE-PHASE.
2. ACCURACY CL.1 (EN 62053).
3. DIRECT MEASUREMENT UP TO 80 A.
4.ENERGY CONSUMPTION LED.
5.CURRENT CHECKING LED.
6.8 DIGITS ELECTRONIC COUNTER.
7.PULSE OUTPUT SO (DIN 43864).
8. 4 DIN MODULE.
TECHNICAL SPECIFICATIONS
Current IB (IMAX) | 10 (80) A |
Burden | < 3 VA |
Operating range | 0-100 % IMAX |
Starting current (In) | < 0,4 % IB |
Rated Voltage (Un) | 3x230 (400) V A.C. |
Burden | < 8 VA, 2 W |
Operating range | ± 15 % Un |
Frequency | 50 - 60 Hz |
CURRENT INPUT
VOLTAGE INPUT
Counter type | Electromechanical |
Digits | 6 + 2 decimal |
Nº of counters | 1 (Total) |
Class | 1 ( EN 62053) |
Operating temperature | - 20 to +55 ºC |
Energy indicator | Flashing LED |
Pulse weight | 1000 pulses / kWh |
Case material | ABS, UL94 V0 |
Dimensions | 4 modules (70 mm) |
Terminals | Sealable |
Connection | With screw |
Max. wire section | |
Phase input terminals | 25 mm |
Mounting | 35 mm DIN rail |
GENERAL FEATURES
THREE-PHASE - INDIRECT INPUT - TI96 - TIV96
Those energy meters used for billing should have MID Certification. Thus, the quality of the instruments is ensured having been necessary to control by a notified body that just it.
1.UNBALANCED 3-PHASE.
2.ACTIVE ENERGY OR ACTIVE ENERGY + REACTIVE ENERGY.
3. CL. 2 ACCURACY (EN 62053).
4.SELECTABLE PRIMARY CURRENT.
5.INSULATED CURRENT (INTERNAL TRANSFORMERS).
6. ENERGY CONSUMPTION LED.
7. 7 DIGITS ELECTROMECHANICAL COUNTER.
8. PULSE OUTPUT (RELAY): SO (DIN 43864).
9. 96 X 96 DIN DIMENSIONS.
TECHNICAL SPECIFICATIONS
Current IB (IMAX) | X/1 or X/5 A |
Burden | < 0,2 VA |
Operating range | 0-100 % IMAX |
Starting current (In) | 1 % IB |
Rated Voltage (Un) | 110, 230, or 400 V C.A. |
Burden | < 1 mA x U phase N |
Operating range | 20-120 % Un |
Frequency | 50 - 60 Hz |
CURRENT INPUT
VOLTAGE INPUT
Accuracy Class 2 (Optional) | Class 2 | Class 1 |
Operating temperature | - 5 to +55 ºC |
Energy indicator | Flashing LED |
Pulse weight | 16 pulses / kWh |
Case materia | Metálica+ABS, UL94 V0 |
Dimensions | DIN 96x96 mm |
Connection | Current inputs, M4 |
Terminals | Pluggable |
Max. wire section | 2,5 mm |
Terminals | Sealable |
GENERAL FEATURES
TOTALIZER TERMINALS TTI /TTIM
TTI: Totalyzer module with the microprocessor and serial output. TTIM: Totalyzer module with a microprocessor and serial output. 128 kB, LCD display, and built-in keypad.
1.8 INDEPENDENT PULSE COUNTERS.
2. INDEPENDENT COUNTER RESET.
3. PROGRAMMABLE COUNTER VALUE.
4. TTIM: 90 DAYS OF LOAD CURVE PER COUNTER.
5. RS485 SERIAL OUTPUT PROGRAMMABLE. (ABLE TO MEASURE CLOSED CONTACT TIME IN. SECONDS, TIME, OR PULSES.
TECHNICAL SPECIFICATIONS
Aux. V | 100, 110, 230 or 400 V C.A |
Burden | 4 VA |
Operating range | 80-120 % Un |
Rated Voltage (Un) | 230 V A.C. |
Burden | < 8 VA, 2 W |
Operating range | ± 15 % Un |
Frequency | 50 - 60 Hz |
AUXILIARY VOLTAGE
VOLTAGE INPUT
Case material | ABS, UL94 V0 |
Dimensions | (9 modules) 155 x 90 |
Terminals | Pluggable |
Max. wire section | 2,5 mm |
Weight | 0,40 kg |
Operating temperature | 5 to +55 ºC |
Electrical safety (EN 61010) | Class 2, Category 3 |
GENERAL FEATURES
MULTIFUNCTION RECORDING METERS CTMRII And CTMRIID
CTMRII and CTMRIID are static meters for a 3-phase connection. They measure active and reactive energy with classes 1 and 2. respectively. Moreover, these meters include built-in recording functions for type 2, 3, and 4 customers. They have a four-line, twenty-character display for data displaying, two buttons, one for bill closures and another for display management, LED diodes for checking active and reactive energy measurement, signal outputs using relays, and pulse emission by solid-state relays. They also have three communication interfaces, a UNE EN 62056-21 optical one, an RS232 electrical one, and an RS232 or RS485 one. The communication protocol is UNE EN 61870-5-102, which can be adapted by the System Operator.
Additionally, the meter has the following information
1.Phase voltage and line voltage.
2.Currents.
3. Active, reactive, and apparent power, global and per phase phi cos.
4. Frequency.
5. Information about software updates.
6. Information about special actions (reset to zero, transformation ratio, and burden curve periods).
7.Backup of the main values.
AVAILABLE INFORMATION
DisplayCounter type | 4x20 LCD alphanumeric characters |
Communication | |
Protocol | published by System Operator |
Optical | According to UNE EN 61107, programmable baud rate up to 9600 bauds, parity programmable |
Local port | RS232 direct or via modem, programmable, speed up to 115200 bauds, parity programmable. |
Operating reserve | 10 years. |
Buttons | 1 sealable for manual reset to zero 1 for display management |
Battery | polarized housing for easy change over |
Dimensions | 1 module (17,5 mm) |
GENERAL FEATURES